Multi Sentry

Power Range

160-200 kVA
  • 3:3

Multi Sentry protects data centres, telecommunications systems, IT networks and other critical systems where a poor power supply would put the continuity of your services at risk. The MST 160 and MST 200 models are three-phase in and out and use on-line double conversion (VFI-SS-111) technology.

Three-level NPC inverters deliver an operating efficiency of up to 96.2%, and unity output power factor gives you the full 160 or 200 kW of active power. A fully controlled IGBT rectifier keeps input current distortion as low as 2.5% with a 0.99 input power factor, so the UPS has virtually zero impact on the mains or a generator.

Up to 8 units can run in parallel for extra capacity or N+1 redundancy. ON LINE, ECO, SMART ACTIVE and STANDBY OFF modes, a Battery Care System for VRLA, AGM, GEL, open vent and Nickel Cadmium batteries, and a backlit graphic display with three communication slots, USB and RS232 come as standard.

Enquire About This Product

Downloads

Characteristics

  • Range 160-200 kVA
  • High efficiency up to 96.2%
  • Zero impact
  • Flexibility of use
  • Advanced communications

Multi Sentry solves installation problems in systems where the power supply has limited power available, where the UPS is supported by a generator or where there are compatibility problems with loads that generate harmonic currents; Multi Sentry has a zero impact on its power source, whether this is the mains power supply or a generator:

  • Input current distortion up to <2.5%;
  • Input power factor 0.99;
  • Power walk-in function that ensures progressive rectifier start up;
  • Start up delay function, to restart the rectifiers when mains power is restored if there are several UPS in the system.

In addition, Multi Sentry plays a filtering and power factor correction role in the power network upstream of the UPS, as it eliminates harmonic components and reactive power generated by the power utilities.

State-of-the-art three-level NPC inverters are used across the power range (160-200 kVA) to achieve an operating efficiency of 96.2%. This technology halves (50%) the energy dissipated in a year by traditional UPS, with an efficiency level of 92%. Its exceptional performance makes it possible to recover the capital investment cost in less than three years of operation.

Proper battery care is critical to ensuring correct UPS operation in emergency conditions. The battery care system consists of a series of features and capabilities to optimise battery management and obtain the best performance and operating life possible.

Battery recharging: Multi Sentry is suitable for use with hermetically sealed lead-acid (VRLA), AGM and GEL batteries and Open Vent and Nickel Cadmium batteries. Depending on the battery type, different charging methods are available:

  • One-level voltage recharge, typically used for widely available VRLA AGM batteries;
  • Two-level voltage recharge according to IU specification;
  • Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries.

Recharge voltage compensation based on temperature in order to prevent excessive battery charges or overheating.

Battery tests to diagnose in advance any reduction in performance or problems with the batteries.

Deep discharge protection: during extended low-load discharges, the end-of-discharge voltage is increased - as recommended by battery manufacturers - to prevent damage or reduced battery performance.

Ripple current: recharge ripple current (residual AC component) is one of the main causes of reduced reliability and battery life.

Using a high frequency battery charger, Multi Sentry reduces this value to negligible levels, prolonging battery life and maintaining high performance over a long period of time. Wide voltage range: the rectifier is designed to operate within a wide input voltage range (up to -40% at half load), reducing the need for battery discharge and thus helping to extend battery life.

Distributed parallel configuration of up to 8 units per redundant (N+1) or power parallel system. The UPS continue to operate in parallel even if the connection cable is interrupted (Closed Loop).

A combination of advanced technology high performance components allows Multi Sentry to provide exceptional performance and efficiency:

  • The type of input stage (IGBT rectifier) ensures an input power factor close to 1 with low current distortion, avoiding the need for bulky and expensive filters;
  • Unity output power factor for MST 160-200 make it suitable to any Data Center application ensuring full power availability no matter what the utilities power factor range (typically from 0.9 lagging to 0.9 leading);
  • More active power than a traditional UPS, guaranteeing a greater margin when sizing UPS for potential future load increases;
  • Smart ventilation principle on MST 160-200 manages the number of operating fans and their speed according to room temperature and load level. This preserves the life span of the fans and at the same time we reduce noise level and overall power consumption for unnecessary UPS ventilation.

With its flexible configuration, performance, accessories and options, Multi Sentry is suitable for use in a wide range of applications:

  • Suitable for powering capacitive loads, such as blade servers, without any reduction in active power from 0.9 lead to 0.9 lag;
  • ON LINE, ECO, SMART ACTIVE and STANDBY OFF operating Modes - compatible with centralised power systems (CPSS) applications;
  • Frequency Converter Mode;
  • Configurable EnergyShare sockets (as standard) to preserve runtime for the most critical loads or to be activated only when mains power fails;
  • Cold Start to switch on the UPS even when there is no mains power present;
  • Optional temperature sensor for external battery cabinets, to assist recharge voltage compensation;
  • High power battery chargers to optimise charge time in the event of long runtimes;
  • Optional dual input mains power supply;
  • Isolation transformers for modifying the neutral earthing (separate power sources), or for galvanic isolation between the input and output;
  • Different sized battery cabinets and capacities, for extended runtimes;
  • MST 160-200 could be equipped with a side mounted top entry cabinet to arrange UPS cabling from the top.

Multi Sentry is equipped with a backlit graphic display (240x128 pixels) providing UPS information, measurements, operating states and alarms in different languages. It can also display waveforms and voltage/current forms.

The default screen displays UPS status, graphically indicating the status of the various assemblies (rectifier, batteries, inverter, bypass).

  • Advanced multi-platform communications for all operating systems and network environments: PowerShield3 monitoring and shutdown software included for Windows operating systems 11, 10, 8, Hyper-V, Server 2022, 2019, 2016 and previous versions, Windows Server Virtualization Hyper-V, macOS, Linux, Citrix XenServer and other Unix operating systems;
  • Compatible with VMware infrastructures to perform graceful shutdown of hosts and clusters; to perform Vmotion and prioritised shutdown of VM thanks to NetMan 208 Network card;
  • Compatible with Nutanix and Syneto infrastructures to perform graceful shutdown of hosts; to perform prioritised shutdown of VM thanks to NetMan 208 Network card;
  • RS232 port and USB ports;
  • 3 slots for the installation of optional communications accessories such as network adapters, potential free contacts, etc.;
  • R.E.P.O. Remote Emergency Power Off for switching off the UPS via a remote emergency button;
  • Input for the connection of the auxiliary contact of an external manual bypass;
  • Input for synchronisation from an external source;
  • Graphic display panel for remote connection.

Technical Specifications

MODELS MST 160
Nominal power [kVA] 160
Rated voltage [V] 380 / 400 / 415 three-phase + N
Rated frequency [Hz] 50 / 60
Voltage tolerance [V] 400 ±20% @ full load
Frequency tolerance [Hz] 40 - 72
Power factor @ full load 0.99
Current distortion THDI ≤3%
Rated voltage [V] 380 / 400 / 415 three-phase + N
Number of phases 3 + N
Voltage tolerance (ph-N) [V] 180 / 264 (selectable)
Rated frequency [Hz] 50 or 60 (selectable)
Frequency tolerance ±5% (selectable)
Bypass overload 125% for 60 min, 150% for 10 min
Nominal power [kVA] 160
Active power [kW] 160
Power factor 1
Number of phases 3 + N
Rated voltage [V] 380 / 400 / 415 three-phase + N (selectable)
Static variation ±1%
Dynamic variation ±3%
Crest factor [lpeack/lrms] 3:1
Voltage distortion ≤1% with resistive linear load / ≤3% with non-linear load
Frequency [Hz] 50 / 60
Frequency stability during battery operation 0.01%
Type VRLA AGM/GEL/NiCd/Li-ion/Supercaps
Recharge time 6 h
Weight without batteries [kg] 450
Dimensions (WxDxH) [mm] 840x1035x1900
Communications 3 slots for communications interface / USB / RS232
Ambient temperature for the UPS 0 °C - +40 °C
Recommended temperature for battery life +20 °C - +25 °C
Range of relative humidity 5-95% non-condensing
Colour RAL 7016
Noise level at 1 m [dBA±2] (SMART ACTIVE ) <50
IP rating IP20
SMART ACTIVE efficiency up to 99%
Standards European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111
Moving the UPS castors